Specifications
Tester
High voltage detector
Host (current clamp)
Range
0.0mA ~ 1200A ( 50/60Hz automatic )
0.0mA ~ 20A
Resolution
0.1mA
0.1mA
Clamp Diameter
φ50mm
φ7.5mm
Test Accuracy
±2%±5dgt
±0.5%±5dgt
Sampling Speed
2 times/second
Function
High-low voltage current transformer primary and secondary loop current, transformation ratio, polarity, phase, and on-line test; current and voltage ratio on both sides of transformer; on-line test; load current test
Transmission type
Wireless transmission, straight line transmission distance 30m
Shift gear
Automatic shift
Power
DC6V 7# Alkaline battery ( 1.5V AAA×4 )
DC7.5V 5# Alkaline battery ( 1.5V LR6×5 )
Test mode
Clamp CT
Meter Dimension
W/T/H: 87*37*262mm
Host: W/T/H:100*35*204mm
Current clamp: W/T/H: 42*20*137mm
Display mode
LCD : 128dots×64dots Blue screen backlight function, suitable for dark places
Ratio
Three kinds of transformation ratio display: (The primary and secondary circuit actually measured the current transformation ratio; the conversion ratio of the secondary circuit 5A; 10kV-YY transformer conversion ratio of 10kV/380V), the maximum ratio of 1:10 million
Line voltage
Line test with insulation sheath below 60kV or bare wire current test below 35kV (must operate with insulation rod)
Lead wire length
The lead wire of the current clamp 2 meter
Weight
Total weight of instrument : 3.1kg ( including insulation rob and instrument bag), High voltage detector : 370g ( including battery), Host : 409g ( including battery ), Current clamp : 180g
Data interface
USB transmission
No signal instruction
“NO SIGNAL —-” is displayed when the host does not receive the transmission signal
Insulated rod
Five section insulation rods (5 meters in total)
Insulation strength
AC 60kV/rms
Line test
Line test with insulation sheath below 60kV or bare wire current test below 35kV (operate with insulation rod)
Production Compliance
IEC61010-1、IEC61010-2-032、Pollution Grade 2、CAT III (600V) IEC61326 (EMC Standard)
IP
IP45